Chapter 6, About mapping, Chapter 6: mapping – Hardy HI 3010 Filler/Dispenser Controller User Manual

Page 81

Advertising
background image

65

CHAPTER 6
Mapping

CHAPTER 6: MAPPING

About Mapping

Mapping is a simple process where you connect an input
(Source) to an output (Destination). The HI 3010 has four
output Relays and five Input Contacts. You can also map
parameter values to and from these outputs and inputs. The
benefit of Mapping is that it requires no programming.

NOTE:

The HI 3000 Series Operation and Installation
Manual provides additional mapping help.

NOTE:

Data is handled based on the method used writ-
ing data to the unit. If data is written using the
Command Interface (See Below) the data is inter-
preted based on the displayed units. However, if
data is directly mapped into the unit, the unit
assumes lbs (pounds) and converts the entered
data to the displayed units.

Mapping to an HI 3010 with a pre-2.3 Firmware Ver-
sion

HI 3010’s with firmware versions older than 2.3 send UDP
packets with data at fixed locations. Some of these words
correspond to words contained in the 2.3+ version, Hardy
Control-Link Table as shown below:

Therefore a version 2.3+ HI 3010 can pick up Gross Wt from
a pre-2.3 HI 3010 node, let’s say Node 7 from 7FI5. Net
Weight at 7FI7. State Machine output word HI2 at 7SI2.
Alarm word 0 at 7SI3.

Mapping to an Output Relay

In English we might say: “Connect the Ingredient Fast Fill
Command to Relay Output #1.

Relay Output #1 is the Destination.

Fast Fill is the Source.

In Assignment Statement form this mapping would look like
this:

Destination = Source or

Output Relay #1 = Fast Fill

From the Web Browser let’s go through the process:

Step 1. From the Filler/Dispenser

Home Page click on Configura-
tion. (See Fig. 6-1) The Config-
uration Page appears. (See Fig.
6-2)

FIG. 6-1 HOME PAGE/SELECTING

CONFIGURATION

Step 2. Click on Mapping Setup. (See Fig. 6-2) The Con-

figuration Mapping Setup Page appears. All the
pull down menus include all the Destinations for
the HI 3010. (See Fig. 6-3)

FIG. 6-2 CONFIGURATION PAGE/SELECTING

MAPPING SETUP

2.3 Word

Pre 2.3 Contents

0

HI0, digital inputs

1

HI1, Status Word

2

HI2, State Machine Output Word 0

3

HI3, Alarms Word 0

4

HI4, Alarms Word 1

5&6

Gross Wt., Floating Point

7&8

Net Wt., Floating Point

9

Packet Sequence Number

TABLE 6-1: HI 3010

Advertising