About the auxiliary device timer, Refill parameters, Discharge menu/auxiliary device timer – Hardy HI 3010 Filler/Dispenser Controller User Manual

Page 50: Setup menu/refill, Refill menu/refill, Refill menu/initial refill

Advertising
background image

HI-3010 Filler/Dispenser/IBC

34

Service Manual

FIG. 4-53 DISCHARGE MENU/AUXILIARY DEVICE

TIMER

About the Auxiliary Device Timer

An example of an Auxiliary Device is a vibrator for a feeder
to correct bridging that can occur with some materials when
being discharged from a vessel. The timer setting sets how
long the Auxiliary Device should remain on until the bridg-
ing condition corrects itself. An Auxiliary Device can be any
device you want to enable. The timer is set based on your
process requirements.

Step 18. Press the right or left arrow buttons to increase or

decrease the time you want the Auxiliary Device to
operate.

Step 19. Press the Enter button to set the entry.
Step 20. Press the Exit button to return to the SETUP

MENU.

Refill Parameters

About the Filler Refill Parameters

The Refill pertains to the vessel that is putting material into
the filler vessel. This vessel must have enough material to
complete one whole fill cycle of all the fill cycles depending
on your application. The refill vessel will probably have
level sensors indicating a high and low level. When you turn
on the Refill the instrument sees the low level sensor, for
example, that is calling for more material. It opens a gate or
valve until the material level reached the high level sensor, at
which time it closes the gate. If you turn on the Initial Refill,
it will make sure that you have enough material at the first
fill cycle. The Refill can operate at any time during filling to
make sure that the refill vessel has enough material for a fill
cycle(s).

NOTE:

You must map the High and Low Level Sensors to
the instrument.

PARAMETER:REFILL
RANGE: OFF/ON
DEFAULT: OFF

PARAMETER:INITIAL REFILL
RANGE: OFF/ON
DEFAULT: OFF

Step 1. Press the down arrow button until the cursor is in

front of Refill. (See Fig. 4-54)

FIG. 4-54 SETUP MENU/REFILL

Step 2. Press the Enter button. The Refill Menu appears

with the cursor in front of Refill. (See Fig. 4-55)

FIG. 4-55 REFILL MENU/REFILL

Step 3. Press the right or left arrow buttons to toggle

between ON and OFF.

Step 4. Press the enter button to set the entry.
Step 5. Press the down arrow button to move the cursor in

front of Initial Refill. (See Fig. 4-56)

FIG. 4-56 REFILL MENU/INITIAL REFILL

Step 6. Press the right or left arrow button to toggle

between OFF and ON.

Step 7. Press the Enter button to set the entry.
Step 8. Press the Exit button to return to the SETUP

MENU.

About the Dispenser/IBC Refill Parameters

The Refill pertains to the Dispensing vessel and is actuated
by the Refill Weight Parameter. The Dispense vessel must
have enough material to complete one whole dispense cycle.
If Refill is on, prior to starting a dispense cycle the instru-
ment checks the weight in the vessel. If the weight in the
vessel is below the Refill Weight it initializes the Refill func-
tion and refills the vessel to the preset Refill Weight, then
starts the dispense cycle(s). The Refill must occur in a preset