Setup menu/refill, Refill menu/refill, Refill menu/initial refill – Hardy HI 3010 Filler/Dispenser Controller User Manual
Page 51: Refill menu/setting refill proof switch, Refill menu/setting refill switch timer

35
CHAPTER 4
Configuration
period of time by setting the Refill Duration parameter. If the
Refill takes more time than the preset Refill Duration the dis-
pense is paused and an alarm appears. In addition to the
Refill parameters you can set the Proof Switch to ON to
determine that the refill gate or valve is open. The Switch
Time sets the time it takes for the Proof Switch valve or gate
to open If the time exceeds the preset Switch Time an alarm
appears saying that the Proof Switch did not open.
PARAMETER:PROOF SWITCH
RANGE: OFF/ON
DEFAULT: OFF
PARAMETER:SWITCH TIME
RANGE: 0-99 SECONDS
DEFAULT: 5 SECONDS
PARAMETER:REFILL WEIGHT
RANGE: 0.01 - 999999
DEFAULT: 1000.0
PARAMETER:REFILL DURATION
RANGE: 0-99 SECONDS
DEFAULT: 60 SECONDS
Step 1. Press the down arrow button until the cursor is in
front of Refill. (See. Fig. 4-57)
FIG. 4-57 SETUP MENU/REFILL
Step 2. Press the Enter button. The Refill Menu appears
with the cursor in front of Refill. (See Fig. 4-58)
FIG. 4-58 REFILL MENU/REFILL
Step 3. Press the right or left arrow buttons to toggle
between ON and OFF.
Step 4. Press the enter button to set the entry.
Step 5. Press the down arrow button to move the cursor in
front of Initial Refill. (See Fig. 4-59)
FIG. 4-59 REFILL MENU/INITIAL REFILL
Step 6. Press the right or left arrow button to toggle
between OFF and ON.
Step 7. Press the Enter button to set the entry.
Step 8. Press the down arrow button to move the cursor in
front of Refill Prf Sw. (See Fig. 4-60)
FIG. 4-60 REFILL MENU/SETTING REFILL PROOF
SWITCH
Step 9. Press the right or left arrow buttons to toggle
between ON and OFF.
Step 10. Press the Enter button to set the entry.
Step 11. Press the down arrow button to move the cursor in
front of Refill Sw Timer. (See Fig. 4-61)
FIG. 4-61 REFILL MENU/SETTING REFILL
SWITCH TIMER
Step 12. Press the left or right arrow button to select the
Refill Switch time.
Step 13. Press the Enter button to set the entry.
Step 14. Press the down arrow button to move the cursor in
front of Refill Wt. (See Fig. 4-62)
>
REFILL MENU
Ref il l ON
Initial Ref il l OFF
Ref il l Pr f Sw ON
>
REFILL MENU
Ref il l ON
Initial Ref il l OFF
Ref il l Pr f Sw ON
>
REFILL MENU
Initial Ref il l OFF
Ref il l Pr f Sw ON
Ref il l Wt 1000.00
>
REFILL MENU
Initial Ref il l OFF
Ref il l Pr f Sw ON
Ref il l Sw Timer 5s