SCPI Command Summary

The SCPI commands supported by this programmable power supply are described in the tables in the
remainder of this section. These tables use the following column headings:

•

Function The commonly used name for the function.

•

SCPI Command The full command in long form.

•

Description Explains what the command does or what is affected by it.

•

Query? Indicates whether the unit supports a query version of the listed command.

•

N/A Indicates Not applicable. (The command has no query form and will respond with an error if
queried.)

Table A-1

IEEE 488.2 Commands

Function

SCPI Command

Description

Parameter and
Range

Query

Select Address

*ADR

Select the power supply unit
to communicate with.

?|<Address (1–30)>

Yes

Clear Status

*CLS [:]STATus[<channel>]:CLEar

Clears all the status data
structures.

N/A

Query the Error
Queue

*ERR

Query the Error Queue for the
oldest error event.

Standard Event
Status Enable
Query

*ESE?
[:]STATus[<channel>]:STANdard:ENABle

Query the Standard Event
Status Enable register
settings.

Yes

Standard Event
Status Enable

*ESE

[:]STATus[<channel>]:STANdard:ENABle
<ESE-word>

Set the Standard Event Status
Enable Register bits.

<Enable Flags(0–
255)>

N/A

Standard Event
Status Register
Query

*ESR?
[:]STATus[<channel>]:STANDard[:EVENt]?

Query the Standard Event
Status Register (SERS).

Yes

Advertising