Yaskawa CM012 DeviceNet Option Card User Manual

Page 25

Advertising
background image

Supported Objects 2-4

‹

Yaskawa Enhanced Control/Modbus Message – Input Instance 105 (69h)

‹

Yaskawa Enhanced Control/Modbus Message – Input Instance 107 (6Bh)

Instance

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

105 (69h)

Enhanced

Control/

MODBUS

Message

8 Bytes

0

0

Terminal

S8

1

Terminal

S7

Terminal

S6

Terminal

S5

Terminal

S4

Terminal

S3

Run

REV

Run

FWD

1

Terminal

P2

2

Terminal

P1

2

Terminal

MA/MB

2

-

Function

Bit 2

3

Function

Bit 1

3

Fault

Reset

External

Fault

1

2

Speed Reference (Scaled by Parameter o1-03)

3

2

4

Register Number

5

3

6

Data

7

Note:

Refer to output instance 155 (9Bh) for response

1

G5, F7 & G7 Only

2

G5 Byte 1

Bit 5 = Terminal 9

Bit 6 = Terminal 25

Bit 7 = Terminal 26

3

Bit 1

Bit 2

Function

0

0

No Function

0

1

Read Register

1

0

Write Register

1

1

No Function

Instance

Word

Byte

Bit 7

Bit 6

Bit 5

Bit 4

Bit 3

Bit 2

Bit 1

Bit 0

107 (6Bh)

Standard

DI/DO

Control

8 Bytes

0

0

Terminal

S8

1

Terminal

S7

Terminal

S6

Terminal

S5

Terminal

S4

Terminal

S3

Run REV

Run FWD

1

-

-

Terminal

S12

3

Terminal

S11

3

Terminal

S10

3

Terminal

S9

3

Fault

Reset

External

Fault

1

2

Terminal

P4

3

Terminal

P3

3

Terminal

P2

2

Terminal

P1

2

Terminal

MA/MB

2

-

-

-

3

-

2

4

Analog Output 1

5

3

6

Speed Reference (Scaled by Parameter o1-03)

7

Note:

1

G5, F7 & G7 Only

2

G5 Byte 2

Bit 3 = Terminal 9

Bit 4 = Terminal 25

Bit 5 = Terminal 26

3

G7 only