Programming 5 - 32

E1-12 Mid Output Voltage B
E1-13 Base Voltage

Setting Range:

0.0 to 255.0V (240V Models)
0.0 to 510.0V (480V Models)

Factory Defaults: 0.0V (240V Models)

0.0V (480V Models)

To set up a custom V/f pattern, program the points shown in the diagram below using parameters E1-04 through E1-13. Be
sure that the following condition is true:

E1-09

E1-07

E1-06

E1-11

E1-04

Fig 5.22 Custom V/f Pattern Programming Curve

Increasing the voltage in the V/f pattern increases the available motor torque. However, when setting a custom V/f pattern,
increase the voltage gradually while monitoring the motor current, to prevent:

Drive faults as a result of motor over-excitation

Motor overheating or excessive vibration

E2 Motor Setup

E2-01 Motor Rated Current

Setting Range:

Model Dependent (see Appendix B)

Factory Default: Model Dependent

The Motor Rated Current parameter (E2-01) is necessary information for the Drive motor protection function. The motor over-
load protection parameter L1-01 is enabled by default. In addition, motor rated current is used by the torque compensation
function to insure optimum torque production. Set E2-01 to the full load amps (FLA) value stamped on the motor’s
nameplate. During Auto-tuning, it is required for the operator to enter the motor rated current in parameter T1-04 on the
Auto-Tuning menu. If the Auto-tuning operation completes successfully, the value entered into T1-04 will be also written into
E2-01.

Frequency

E1-09 E1-07

E1-06

E1-04

E1-11

Max Voltage E1-05

Mid Voltage B E1-12

Mid Voltage A E1-08

Base Voltage E1-13

Min Voltage E1-10

Min

Freq

Max

Freq

Base

Freq

Mid

Freq

A

Mid

Freq B

Freq A

TM_E7_01_07182008.book Page 32 Wednesday, July 23, 2008 2:35 PM