Diagnostic & Troubleshooting 6 - 8

UV2

CTL PS Undervolt

Control Power Supply Undervoltage

Undervoltage of the control circuit when

running

External load connected

pulling down the Drive power

supplies

Cycle power off and on to the
Drive

Repair or replace the Power PCB/
Gate Drive PCB

Remove all control wiring and
test Drive

UV3

MC Answerback

Soft Charge Circuit Fault

The pre-charge contactor opened while the

Drive was running

Contacts on the soft charge

contactor are dirty and the soft

charge contactor does not

function mechanically

Cycle power off and on to the
Drive

Check the condition of the soft
charge contactor

Repair or replace the Power PCB/
Gate Drive PCB

WARNING

Some features within the PI function group cause the Drive to shut down momentarily (e.g. Sleep Function,
Snooze Function, Feedback Loss feature etc.) Upon recovery from the conditions that activate these features,
the Drive may start unexpectedly. Therefore, when enabling these features take appropriate measures to
notify personnel working with this equipment that unexpected starting may occur.

Table 6.1 Fault Displays and Processing

Digital

Operator Display

Description

Cause

Corrective Action