Parameters A - 26

Monitor List

Table A.2 Monitor List

Parameter

No.

Parameter Name

Digital Operator Display

Description

Monitor

U1-01

Frequency Reference
Frequency Ref

Frequency reference (speed command) monitor when in auto
mode, frequency reference (speed command) setting location
when in hand mode. Units changeable via o1-03.

U1-02

Output Frequency
Output Freq

Output frequency (speed) monitor. Units changeable
via o1-03.

U1-03

Output Current
Output Current

Output current monitor

U1-06

Output Voltage
Output Voltage

Displays Drive output voltage

U1-07

DC Bus Voltage
DC Bus Voltage

Displays DC Bus Voltage

U1-08

Output Power
Output kWatts

Displays Drive output power

U1-10

Input Terminal Status
Input Term Sts

Displays Drive input terminal status

U1-11

Output Terminal Status
Output Term Sts

Output terminal ON/OFF Check

U1-12

Drive Operation Status
Int Ctl Sts 1

0

1: FWD. run

(Terminal S1) is ON

1: REV. run

(Terminal S2) is ON

1: Multi-function input 1

(Terminal S3) is ON

1: Multi-function input 2

(Terminal S4) is ON

1: Multi-function input 3

(Terminal S5) is ON

1: Multi-function input 4

(Terminal S6) is ON

0 0 0 0 0 0 0

1: Multi-function Contact 1

output 1 (Terminal M1-M2)
is ON

1: Multi-function Contact 2

output 1 (Terminal M3-M4)
is ON

Not used

1: Fault output

(Terminal MA/MB) is ON

0 0 0 0 0 0 0 0

1: During running

1: During zero speed

1: During reverse

1: During reset signal input

1: During speed agree

1: Drive operation ready

1: During fault detection

(Minor fault)

1: During fault detection

(Major fault)

0 0 0 0 0 0 0 0

TM_E7_01_07182008.book Page 26 Wednesday, July 23, 2008 2:35 PM