The following additional information must be followed when performing Electrical Hook-Up of a
DSD 406 or DSD 412 drive, according to the procedures listed on pages 12-15 of technical manual
TM 6107, dated 4/15/94.

– Although the three phase input power line is fuse protected internal to the drive, it is recommended to provide
branch circuit protection by means of a circuit breaker in accordance with the National Electrical Code, local codes
and with a rating of not less than 5,000 rms Symmetrical Amperes and 600 Volts for 2 to 25 Hp rated drives or 10,000
rms Symmetrical Amperes and 600 Volts for 30 to 60 Hp rated drives.

– Electronic overload protection is provided as part of the standard DSD product. It is electronically timed and will
shut down the drive along a time/output current curve which provides shutdown at 60 seconds at 150% or 10
seconds at 200% of rated output current. An overload relay may be added external to the drive in accordance with
the National Electrical Code and local codes for additional protection.

– Main Circuit Input/Output Wire Sizing:

L1-3: Using 600V vinyl-sheathed wire per the following table.

Recommended Wire Gauge (Copper Only)

Torque

Drive Hp

60°C

75°C

(in-lbs)

2

14

14

35

3

14

14

35

5

14

14

35

7

8

10

40 - 35 *

10

8

10

40 - 35 *

15

6

8

45 - 40 *

20

6

8

45 - 40 *

25

4

4

45

30

4

4

45

40

1

150

50

1

150

60

1/0

180

75

3/0

250

100

3/0

250

125

250 MCM

325

150

600 MCM

375

200

600 MCM

375

* Torque per wire gauge.

Effective 02/06/95

PAGE 1

TM 6107 Addendum 1

© Copyright 1995 MagneTek, Inc.