Yaskawa DSD 406 User Manual

Page 76

Advertising
background image

Fault/Error

Possible Causes &

Code

Fault/Error Name

Corrective Actions

Table 3. Troubleshooting Guide – Continued

909

(continued)

910

911

912

915

Blown Fuse Fault

Shorted or leaky SCR

Open SCR Fault

Bad Set-Up Parameter Fault

a. Replace Armature Interface PCB.

See “Replacing Armature Interface
PCB”/Maintenance Section.

b. Replace main PCB. See “Replacing

Drive Control PCB”/Maintenance
Section.

Main Fuses blown:
1.

Power Circuit problem; shorts or loose
connections.

2.

Faulty SCR.

3.

Poor regulator tuning.

Check power circuit for shorts or loose
connections and repair.

Test for defective SCR(s) and replace as
necessary.

See “Replacing Fuse(s)”/Maintenance
Section. PERFORM THIS STEP
LAST.

1. Loose gate lead connector.
2. Bad

SCR.

3.

Faulty Armature PCB.

Replace faulty SCR.

Replace Armature Interface PCB.
See “Replacing Armature Interface
PCB”/Maintenance Section.

One or more of the drive’s set-up
parameters is not in the range of
the HP selected:

Rated AC line volts setting is out of
range.

Rated Motor Armature Volts setting
is out of range.

Rated Load Current Setting is out of
range.

Rated Source Frequency Setting is
out of range.

Rated Field Current setting is out of
range.

IST setting is too high.

Access the Fault or Error List to
determine the faulty parameter(s), and the
corresponding fault(s)/error(s).

4

Maintenance

3/21/96

72

Troubleshooting Guide