Fault/Error

Possible Causes &

Code

Fault/Error Name

Corrective Actions

Table 3. Troubleshooting Guide – Continued

909

(continued)

910

911

912

915

●

Blown Fuse Fault

●

Shorted or leaky SCR

●

Open SCR Fault

●

Bad Set-Up Parameter Fault

❸

a. Replace Armature Interface PCB.

See “Replacing Armature Interface
PCB”/Maintenance Section.

b. Replace main PCB. See “Replacing

Drive Control PCB”/Maintenance
Section.

Main Fuses blown:
1.

Power Circuit problem; shorts or loose
connections.

2.

Faulty SCR.

3.

Poor regulator tuning.

➊

Check power circuit for shorts or loose
connections and repair.

❷

Test for defective SCR(s) and replace as
necessary.

❸

See “Replacing Fuse(s)”/Maintenance
Section. PERFORM THIS STEP
LAST.

1. Loose gate lead connector.
2. Bad

SCR.

3.

Faulty Armature PCB.

➊

Replace faulty SCR.

❷

Replace Armature Interface PCB.
See “Replacing Armature Interface
PCB”/Maintenance Section.

One or more of the drive’s set-up
parameters is not in the range of
the HP selected:

●

Rated AC line volts setting is out of
range.

●

Rated Motor Armature Volts setting
is out of range.

●

Rated Load Current Setting is out of
range.

●

Rated Source Frequency Setting is
out of range.

●

Rated Field Current setting is out of
range.

●

IST setting is too high.

➊

Access the Fault or Error List to
determine the faulty parameter(s), and the
corresponding fault(s)/error(s).

4

Maintenance

3/21/96

72

Troubleshooting Guide