Electrical Hook-Up

3/21/96

ARM (–): Using 600V vinyl-sheathed wire per the following table.

ARM (+): Using 600V vinyl-sheathed wire per the following table.

Field Current Wire Sizing: The recommended conductor for field current
ratings between 10.0 Ampere and 16.0 Ampere is 12 AWG. The
recommended conductor for field current ratings below 10.0 AMpere is 14
AWG. use 600 V vinyl-sheathed 105°C wire or equivalent. The
recommended torques on the field lugs for 14-10 AWG is 25 in-lbs.

Recommended Wire Gauge (Copper Only)

Torque

Drive Hp

60°C

75°C

90°C

(in-lbs)

2

14

14

35

3

14

14

35

5

14

14

35

7

6

8

45 - 40 *

10

6

8

45 - 40 *

15

4

4

45

20

4

4

45

25

3

50

30

3

50

40

1/0

50

50

1/0

50

60

3/0

50

75

250 MCM

325

100

250 MCM

325

125

350 MCM

325

150

500 MCM

375

200

750 MCM

375

* Torque per wire gauge.

Recommended Wire Gauge (Copper Only)

Torque

Drive Hp

60°C

75°C

90°C

(in-lbs)

2

14

14

35

3

14

14

35

5

14

14

35

7

6

8

45 - 40 *

10

6

8

45 - 40 *

15

4

4

45

20

4

4

45

25

3

50

30

3

50

40

1/0

180

50

1/0

180

60

3/0

250

75

250 MCM

325

100

250 MCM

325

125

350 MCM

325

150

500 MCM

375

200

700 MCM

375

* Torque per wire gauge.