4

Maintenance

75

Troubleshooting Guide

3/21/96

Fault/Error

Possible Causes &

Code

Fault/Error Name

Corrective Actions

Table 3. Troubleshooting Guide – Continued

924

925

926

Field Current Setting Error

Field Sense Resistor Fault

PCU Watchdog Timeout Fault

Setting for Rated Field Current is not
within a range based on the version of Field
Interface PCB present in the power cube.
See “Field Interface PCB Ratings”/
Maintenance Parts List. Also see the
possible causes for F925.

➊

Check setting and adjust as required.

1.

Connector J13 is out of place.

2.

Faulty Field Interface PCB.

3.

Faulty DSD Drive Control PCB.

➊

Verify J13 is in proper location.

❷

Replace Field Interface PCB.

❸

Replace Drive main PCB.
See “Replacing DSD Drive Control
PCB”/Maintenance Section.

1.

Problem with either hardware or
software on the DSD Drive Control
PCB.

2.

Ambient noise near the drive's main
PCB.

➊

Electromagnetic noise near the drive's
main PCB may be the cause. Record the
situations during which this fault
occurred. Eliminate noise.

❷

Contact MagneTek for assistance.