4

Maintenance

75

Troubleshooting Guide

3/21/96

Fault/Error

Possible Causes &

Code

Fault/Error Name

Corrective Actions

Table 3. Troubleshooting Guide – Continued

924

925

926

Field Current Setting Error

Field Sense Resistor Fault

PCU Watchdog Timeout Fault

Setting for Rated Field Current is not
within a range based on the version of Field
Interface PCB present in the power cube.
See “Field Interface PCB Ratings”/
Maintenance Parts List. Also see the
possible causes for F925.

Check setting and adjust as required.

1.

Connector J13 is out of place.

2.

Faulty Field Interface PCB.

3.

Faulty DSD Drive Control PCB.

Verify J13 is in proper location.

Replace Field Interface PCB.

Replace Drive main PCB.
See “Replacing DSD Drive Control
PCB”/Maintenance Section.

1.

Problem with either hardware or
software on the DSD Drive Control
PCB.

2.

Ambient noise near the drive's main
PCB.

Electromagnetic noise near the drive's
main PCB may be the cause. Record the
situations during which this fault
occurred. Eliminate noise.

Contact MagneTek for assistance.