Installation and Start-Up

14

Electrical Hook-Up

3/21/96

Ensure that wire size and disconnect devices conform to the installation
contractor’s drawings and to all applicable codes.

●

Although the three phase input power line is fuse protected internal to the
drive, it is recommended to provide branch circuit protection by means of a
circuit breaker in accordance with the National Electrical Code, local codes
and with a rating of not less than 5,000 rms Symmetrical Amperes and 600
Volts for 2 to 25 Hp rated drives or 10,000 rms Symmetrical Amperes and
600 volts for 30 to 60 Hp rated drives.

●

Electronic overload protection is provided as part of the standard DSD
product. It si electronically timed and will shut down the drive along a
time/output current curve which provides shutdown at 60 seconds at 150%
or 10 seconds at 200% of rated output current. An overload relay may be
added external to the drive in accordance with the National Electrical Code
and local codes for additional protection.

●

Main Circuit Input/Output Wire Sizing:

L1-3: Using 600V vinyl-sheathed wire per the following table.

Electrical

Hook-Up

Recommended Wire Gauge (Copper Only)

Torque

Drive Hp

60°C

75°C

(in-lbs)

2

14

14

35

3

14

14

35

5

14

14

35

7

8

10

40 - 35 *

10

8

10

40 - 35 *

15

6

8

45 - 40 *

20

6

8

45 - 40 *

25

4

4

45

30

4

4

45

40

1

150

50

1

150

60

1/0

180

75

3/0

250

100

3/0

250

125

250 MCM

325

150

600 MCM

375

200

600 MCM

375

* Torque per wire gauge.