Electrical hook-up – Yaskawa DSD 406 User Manual

Page 18

Advertising
background image

2

Installation and Start-Up

14

Electrical Hook-Up

3/21/96

Ensure that wire size and disconnect devices conform to the installation
contractor’s drawings and to all applicable codes.

Although the three phase input power line is fuse protected internal to the
drive, it is recommended to provide branch circuit protection by means of a
circuit breaker in accordance with the National Electrical Code, local codes
and with a rating of not less than 5,000 rms Symmetrical Amperes and 600
Volts for 2 to 25 Hp rated drives or 10,000 rms Symmetrical Amperes and
600 volts for 30 to 60 Hp rated drives.

Electronic overload protection is provided as part of the standard DSD
product. It si electronically timed and will shut down the drive along a
time/output current curve which provides shutdown at 60 seconds at 150%
or 10 seconds at 200% of rated output current. An overload relay may be
added external to the drive in accordance with the National Electrical Code
and local codes for additional protection.

Main Circuit Input/Output Wire Sizing:

L1-3: Using 600V vinyl-sheathed wire per the following table.

Electrical

Hook-Up

Recommended Wire Gauge (Copper Only)

Torque

Drive Hp

60°C

75°C

(in-lbs)

2

14

14

35

3

14

14

35

5

14

14

35

7

8

10

40 - 35 *

10

8

10

40 - 35 *

15

6

8

45 - 40 *

20

6

8

45 - 40 *

25

4

4

45

30

4

4

45

40

1

150

50

1

150

60

1/0

180

75

3/0

250

100

3/0

250

125

250 MCM

325

150

600 MCM

375

200

600 MCM

375

* Torque per wire gauge.