Troubleshooting Guide

3/21/96

Fault/Error

Possible Causes &

Code

Fault/Error Name

Corrective Actions

Table 3. Troubleshooting Guide – Continued

266

267

268

269

270

271

272

273

274

Unexpected Null Block

Wrong S-Record Type

Bad S-Record Check

Bad S-Record End Record

File Too Large

Wrong File Name

No Memory Here

NVRAM Protected

Motor Running

YMODEM transfer is stopped. The
YMODEM protocol has been violated. A
null block was received but not expected.

➊

Re-initialize up load procedures on the
YMODEM software and the drive and try
to start again.

YMODEM transfer is stopped. The
program information data is corrupted.

➊

Try again from backup file.

❷

Recompile PAC program.

YMODEM transfer is stopped. The file to
be transmitted is too large to fit in drive’s
memory.

➊

PAC program is too large. Redo,
recompile and try again.

YMODEM transfer is stopped. The
parameter file sent does not belong to the
drive.

➊

Verify the file belongs to the drive and
try again.

YMODEM transfer is stopped. The file
attempted to write to non-existent memory.

➊

Verify drive type in PAC file is correct.

❷

Replace drive PCB or flash ROM chips.
See “Replacing Drive Control PCB”/
Maintenance Section.

YMODEM transfer is stopped. The
NVRAM switch is set to write protect the
NVRAMs.

➊

Put the NVRAM Protection switch to the
“off” position and retry transfer.

YMODEM transfer is stopped. The motor
was running during an operation that
required the motor to be stopped.

➊

Verify that the motor is not being pulled
by its load.

❷

Stop motor and retry the transfer.