Yaskawa DSD 406 User Manual

Page 71

Advertising
background image

4

Maintenance

67

Troubleshooting Guide

3/21/96

Fault/Error

Possible Causes &

Code

Fault/Error Name

Corrective Actions

Table 3. Troubleshooting Guide – Continued

266

267

268

269

270

271

272

273

274

Unexpected Null Block

Wrong S-Record Type

Bad S-Record Check

Bad S-Record End Record

File Too Large

Wrong File Name

No Memory Here

NVRAM Protected

Motor Running

YMODEM transfer is stopped. The
YMODEM protocol has been violated. A
null block was received but not expected.

Re-initialize up load procedures on the
YMODEM software and the drive and try
to start again.

YMODEM transfer is stopped. The
program information data is corrupted.

Try again from backup file.

Recompile PAC program.

YMODEM transfer is stopped. The file to
be transmitted is too large to fit in drive’s
memory.

PAC program is too large. Redo,
recompile and try again.

YMODEM transfer is stopped. The
parameter file sent does not belong to the
drive.

Verify the file belongs to the drive and
try again.

YMODEM transfer is stopped. The file
attempted to write to non-existent memory.

Verify drive type in PAC file is correct.

Replace drive PCB or flash ROM chips.
See “Replacing Drive Control PCB”/
Maintenance Section.

YMODEM transfer is stopped. The
NVRAM switch is set to write protect the
NVRAMs.

Put the NVRAM Protection switch to the
“off” position and retry transfer.

YMODEM transfer is stopped. The motor
was running during an operation that
required the motor to be stopped.

Verify that the motor is not being pulled
by its load.

Stop motor and retry the transfer.