Yaskawa DSD 406 User Manual

Page 74

Advertising
background image

Fault/Error

Possible Causes &

Code

Fault/Error Name

Corrective Actions

4

Maintenance

70

Troubleshooting Guide

3/21/96

Table 3. Troubleshooting Guide – Continued

902

(continued)

903

904

905

Line Sync Loss Fault

Low Line Fault

Field Loss Fault

Check wiring and repair as necessary.

Check boards for shorts and replace as
necessary.

a. Check output of 1PT
b. Check and replace fuses as necessary.

See “Replacing Fuse(s)”/Maintenance
Section.

c. Check wiring and repair as necessary.
d. Check transformer and replace as

necessary

Replace DSD Power Supply. See
“Replacing the Power Supply”/
Maintenance Section.

1. Excessively noisy or intermittent

power connections.

2. Faulty voltage dividers on Armature

Interface PCB.

3. Loss of 3 phase or 1 phase power.

Check power input for problems.

Replace Armature Interface PCB. See
“Replacing Armature Interface
PCB”/Maintenance Section.

1. Power line dips.

a. 1 cycle below 50%.
b. 2 cycles below 70%.
c. 3 cycles below 80%.

2. Loss of power fuse.

Check input power for problems.

Check for blown fuses. See “Replacing
Fuse(s)”/Maintenance Section.

1. Motor field or wiring open.

2. a. Wrong trip level set.

b. Field Economy set too low.

Check motor and wiring.

a. Check trip level setting.
b. Change economy setting as required.

Advertising