Yaskawa DSD 406 User Manual

Page 77

Advertising
background image

4

Maintenance

73

Troubleshooting Guide

3/21/96

Fault/Error

Possible Causes &

Code

Fault/Error Name

Corrective Actions

Table 3. Troubleshooting Guide – Continued

916

917

918

919

Forcing Fault

●

Reverse Armature Voltage Connection Fault

IST Setting Error

Line Voltage Setting Error

No rotation was selected while the loop
contactor was energized.

➊

Stop drive and re-enter Forcing mode.

The polarity of the armature voltage feed-
back is reversed or missing.

➊

Check polarity of wiring.

❷

Replace Armature Interface PCB.
See “Replacing Armature Interface PCB”/
Maintenance Section.

Setting for IST is above hardware
limitations of approximately 325% of rated
drive armature current.

➊

Check setting and adjust as required.

Setting for Rated Line Voltage is not within
the acceptable range of 160-525 VAC or
zero (which will allow the drive to decide if
the input voltage is either 230 or 460 VAC).

➊

Check setting and adjust as required.