Yaskawa DSD 406 User Manual

Page 77

Advertising
background image

4

Maintenance

73

Troubleshooting Guide

3/21/96

Fault/Error

Possible Causes &

Code

Fault/Error Name

Corrective Actions

Table 3. Troubleshooting Guide – Continued

916

917

918

919

Forcing Fault

Reverse Armature Voltage Connection Fault

IST Setting Error

Line Voltage Setting Error

No rotation was selected while the loop
contactor was energized.

Stop drive and re-enter Forcing mode.

The polarity of the armature voltage feed-
back is reversed or missing.

Check polarity of wiring.

Replace Armature Interface PCB.
See “Replacing Armature Interface PCB”/
Maintenance Section.

Setting for IST is above hardware
limitations of approximately 325% of rated
drive armature current.

Check setting and adjust as required.

Setting for Rated Line Voltage is not within
the acceptable range of 160-525 VAC or
zero (which will allow the drive to decide if
the input voltage is either 230 or 460 VAC).

Check setting and adjust as required.