ProSoft Technology 5201-DFNT-104C User Manual

Page 20

Advertising
background image

Configuring the Gateway

104C Version 3 ♦ ProLinx Gateway

Protocol Manual

IEC 60870-5-104 Client (Firmware v3.xx)

Page 20 of 139

ProSoft Technology, Inc.

August 4, 2011

Time DB Offset
-1 or 0 to 3994
This parameter sets the location in the database where the gateway’s

104C

Client date and time will be copied to.

Note: The following table lists the 12-byte data area placed in the database if the Time DB Offset
parameter is set to a value other than -1:

Byte

Length

Range

Description

0 to 1

2

0 to 59,999

Seconds and milliseconds

2

1

0 to 59

Minutes

3

1

0 to 23

Hour

4

1

Reserved

5

1

1 to 31

Day of the month

6

1

1 to 12

Month

7 to 8

2

0 to 65,535

Year (four-digit format, for example 2005)

9

1

Reserved

10

1

0 or 1

Invalid flag (0 = Valid, 1 = Invalid)

11

1

Reserved

Driver Status Offset
0-3982
Database location of general client driver status data
Disable = -1
Refer to section 6.3 (Server Error and Status Data) for the detailed contents of
the status block.

NOTE: requires 18 registers

Mailbox Offset
0 - 3872
Database offset to the mailbox interface area. This feature is applicable to the
5201-DFNT-104C module. The mailbox allows the DFNT driver to request
specific tasks from the 104 driver such as time update and dynamically sending
commands
Disable = -1
Refer to section 4 (Mailbox feature) for further information about the mailbox
functionality.

The mailbox interface requires 128 database registers.

Advertising