ProSoft Technology 5201-DFNT-104C User Manual
Page 23

104C Version 3 ♦ ProLinx Gateway
Configuring the Gateway
IEC 60870-5-104 Client (Firmware v3.xx)
Protocol Manual
ProSoft Technology, Inc.
Page 23 of 139
August 4, 2011
Response Timeout
0 to 5000 milliseconds DEFAULT VALUE = 5000
This parameter sets the maximum number of milliseconds to wait for a
confirmation from the controlled station to a request from this module to
application level messages.
ACTTERM with Set Point
Y - Y
ES
or N - N
O
This parameter determines if an ACTTERM (Activation Termination) will be sent.
If the parameter is set to Y
ES
, then Set point commands will issue an ACTTERM
when the command is complete. If the parameter is set to N
O
, ACTCON
(Activation Confirmation) is the last response to a Set point command.
Status Offset
Range -1 to 3956
Database location of client status data
Range = 0 - 3956
Disable = -1
(Refer to the status section for further information about the content of this
section).
NOTE: requires 44 registers