Configuring the Gateway

104C Version 3 ♦ ProLinx Gateway

Protocol Manual

IEC 60870-5-104 Client (Firmware v3.xx)

Page 30 of 139

ProSoft Technology, Inc.

August 4, 2011

Poll Interval
This parameter is used if the Enable Code field is set as Enabled With Poll
Interval. It sets the minimum number of seconds to delay between successive
execution of the command.

Session
This parameter is utilized to associate the command with one of the
sessions/clients defined for the module.

Sector
This parameter is used to associate the command with the proper sector of the
selected session.

Data Type
This parameter is used to set the ASDU data type to be used with the message.
The codes specified are those defined for the IEC-870-5-101 protocol. The
following is a listing of command control data types supported in this module:

Type Description

---- -------------------------------------------------

45 Single point command

46 Double point command

47 Regulating step point command

48 Setpoint, normalized point command

49 Setpoint, scaled point command

50 Setpoint, short float point command

51 Bitstring (32-bits) point command

100 General or group interrogation command

101 Counter interrogation command

102 Read command

103 Clock synchronization command

105 Reset process command

107 Test command (IEC-870-5-104 type)

110 Parameter setting for normalized measured value

111 Parameter setting for scaled measured value

112 Parameter setting for short float value

113 Parameter activation command