ProSoft Technology 5201-DFNT-104C User Manual
Page 28

Configuring the Gateway
104C Version 3 ♦ ProLinx Gateway
Protocol Manual
IEC 60870-5-104 Client (Firmware v3.xx)
Page 28 of 139
ProSoft Technology, Inc.
August 4, 2011
2.1.6 [IEC-60870-5-104 Client Commands]
Each row of this section allows the configuration of one command to be sent to
the remote server. The command can be either a control point (single point,
double-point, etc..) or a general command such as clock synchronization to a
specific client.
The following parameters must be configured for each command:
Enable Code
This field determines when the command will be executed according to the
following codes:
Value
Description
Disabled
Command is disabled and will only execute if enabled from mailbox interface (see mailbox
interface for further details)
Enabled with
Poll Interval
Command will execute no more frequently than the time set in the Poll interval parameter
Conditional
Command will execute when the last value read in the database differs from the current
value