104C Version 3 ♦ ProLinx Gateway

IEC-60870-5-104 Protocol Implementation

IEC 60870-5-104 Client (Firmware v3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 51 of 139

August 4, 2011

M_DP_NA
A Monitor Double-Point information object occupies two bits and uses bit
addressing. It typically represents the ON/OFF states where:
00 = Undefined or invalid
01 = OFF
10 = ON
11 = Undefined or invalid
If you configured the following information objects as shown:

The following table describes how these information objects would be stored in
the gateway memory database.

Inf. Object Address

Module Database Address

200

Bit 0 & 1 of word 120 (Bit address 1920 & 1921)

201

Bit 2 & 3 of word 120 (Bit address 1922 &1923)

202

Bit 4 & 5 of word 120 (Bit address 1924 & 1925)