Point Index
This parameter specifies the Information Object Address in the server device that
corresponds to the command.

Qualifier Parameter
This parameter specifies qualifiers required by the command. This parameter is
dependent on the ASDU data type associated with the command as follows:

SINGLE POINT (45), DOUBLE POINT (46) AND REGULATING STEP (47):

Value:
Single Point Value:
0=Off
1=On

Double Point Value:
0=Not permitted
1=Off
2=On
3=Not Permitted

Regulating Point Value:
0=Not permitted
1=Next step lower if database point is set to -1
2=Next step high if database point set to +1
3=Not Permitted

Qualifier used:
Qualifier Code:
0=No additional definition (slave dependent)
4=Short pulse duration
8=Long pulse duration
12=Persistent output

Select/Execute:
0=Direct execution without select
128=Select executed followed by execute
256=Deselect command

Use Override Flag:
0=Use value in database for value
512=Use override value for state

NORMALIZED (48), SCALED (49) AND SHORT FLOAT (50) SETPOINTS:

Value:
Value read from database for point specified