IEC-60870-5-104 Protocol Implementation

IEC 60870-5-104 Client (Firmware v3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 57 of 139

August 4, 2011

3.4

Using Control (Command) Information Objects

In order to configure the control points please refer to the Client Command
section. Refer to section 2.1.6 for further information about each command field.


The 104C gateway supports the following Control information objects for data
transfer:

ASDU Type

Information Object Description

C_SC_NA

Control Single Command

C_DC_NA

Control Double Command

C_RC_NA

Control Regulating Step Command

C_BO_NA

Control 32-Bit Bitstring Command

C_SE_NA

Control Normalized Value Set Point Command

C_SE_NB

Control Scaled Value Set Point Command

C_SE_NC

Control Short Floating-Point Value Set Point Command


In addition to these the module also supports generic commands to request
specific tasks from the remote server such as clock synchronization.
Each Control information object is identified by its Information Object Address.
For each Control information object, configure the following parameters:
Point Index - This is the Information Object Address of the information object. It
identifies the information object in the network. This address must be unique for
each sector (Common ASDU Address) in the network.
DB Address - This is the database location in the 104C v3 gateway associated
with the information object. The database address interpretation may be bit-
address, byte-address, word-address, double-word-address depending on the
ASDU type. Refer to the following section for further information: