M_BO_NA
A Monitor 32-Bit Bitstring information object occupies two words and uses
double-word addressing.
For example, if you configured the following information objects:

The following table describes how these information objects would be stored in
the gateway memory database.

Inf. Object Address

Module Database Address

600

Words 2000 and 2001 (Double-word address 1000)

601

Words 2002 and 2003 (Double-word address 1001)

602

Words 2004 and 2005 (Double-word address 1002)