ProSoft Technology 5201-DFNT-104C User Manual
Page 58

IEC-60870-5-104 Protocol Implementation
104C Version 3 ♦ ProLinx Gateway
Protocol Manual
IEC 60870-5-104 Client (Firmware v3.xx)
Page 58 of 139
ProSoft Technology, Inc.
August 4, 2011
3.4.1 Control Information Objects Addressing
You must associate each control information object to a database address in the
gateway. The interpretation of the DB Address parameter in the configuration
tables depends on the ASDU configured and the type of addressing associated
with that ASDU.
ASDU Type
Data Size
Addressing Type
C_SC_NA
1 bit
Bit
C_DC_NA
2 bits
Bit
C_RC_NA
1 byte
Byte
C_BO_NA
2 words
Double word
C_SE_NA
1 word
Word
C_SE_NB
1 word
Word
C_SE_NC
2 words
Double word
C_SC_NA
A Control Single Command information object occupies one bit and uses bit
addressing. For example, if you configure the following information objects:
These information objects would be used as follows:
Inf. Object Address
Module Database Address
800
Bit 0 of word 200 to hold the Control bit (Bit address
3200)