ProSoft Technology 5201-DFNT-104C User Manual

Page 75

Advertising
background image

104C Version 3 ♦ ProLinx Gateway

Mailbox Feature (x201-DFNT-104C)

IEC 60870-5-104 Client (Firmware v3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 75 of 139

August 4, 2011

3

Reserved

This field is reserved for future use
and is added here to keep the
structure double-word aligned for all
platforms.

4 to 5

Point Index

This field contains the point index in
the remote device that generated the
event.

6

ASDU Type

This field contains the ASDU type
code for the data contained in the
message.

7

Milliseconds and
Seconds

This word contains the seconds and
milliseconds when the event
occurred.

8

Minutes and Hours This field contains the minutes and

hours the event occurred.

9

Month and Day

This field contains the month and day
of the month the event occurred.

10

Year

This field contains the year the event
occurred.

11

Qualifier

This field contains the point qualifier,
quality or sequence value as
described in the protocol
specification.

12 to 13

Value

This field contains the a double word
value for the point associated with the
event message.