IEC-60870-5-104 Protocol Implementation

104C Version 3 ♦ ProLinx Gateway

Protocol Manual

IEC 60870-5-104 Client (Firmware v3.xx)

Page 56 of 139

ProSoft Technology, Inc.

August 4, 2011

M_ME_NC and M_IT_NA
The Monitor Short Floating-Point Measured Value and Monitor Integrated Totals
information objects occupy two words with double-word addressing.
For example, if you configured the following information objects:

The following table describes how these information objects would be stored in
the gateway.

Inf. Object Address

Module Database Address

500

Words 40 and 41 (Double-word address 20)

501

Words 64 and 65 (Double-word address 32)

502

Word 104 and 105 (Double-word address 52)