Monitor Normalized Measured information objects use a data representation
defined by the protocol specification to represent fractional decimal values. The
following table describes the value for each bit as a reciprocal power of two (2),
that is two (2) raised to the power of a negative exponent (-1 through -15). Bit 15
is the Sign Bit.

Bit

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

Value
Hex(h)
Decimal

Sign

4000h
2

-1

2000h
2

-2

1000h
2

-3

800
h
2

-4

400
h
2

-5

200
h
2

-6

100
h
2

-7

80
h
2

-8

40
h
2

-9

20
h
2

-10

10
h
2

-11

8h
2

-12

4h
2

-13

2h
2

-14

1h
2

-15

4000h
0.5

0

1

0

0

0

0

0

0

0 0 0 0 0 0 0 0

2000h
0.25

0

0

1

0

0

0

0

0

0 0 0 0 0 0 0 0

1000h
0.125

0

0

0

1

0

0

0

0

0 0 0 0 0 0 0 0

6000h
0.75

0

1

1

0

0

0

0

0

0 0 0 0 0 0 0 0

3210h
0.395751953125

0

0

1

1

0

0

1

0

0 0 0 1 0 0 0 0

Examples:
A value of 4000hex (only Bit 14 set, all others clear) is interpreted as 0.5 decimal
A value of 2000hex (only Bit 13 set, all others clear) is interpreted as 0.25
decimal
A value of 1000hex (only Bit 12 set, all others clear) is interpreted as 0.125
decimal
... and so on until...
A value of 0001hex (Only Bit 0 set, all others clear) is interpreted as
0.000030517578125
Therefore, the actual data values transmitted may be any combination of the
decimal values for any given bit pattern.