104C Version 3 ♦ ProLinx Gateway
Mailbox Feature (x201-DFNT-104C)
IEC 60870-5-104 Client (Firmware v3.xx)
Protocol Manual
ProSoft Technology, Inc.
Page 81 of 139
August 4, 2011
4.6
Command List Error Data Mailbox (9950)
Mailbox ±9950 identification code is used to request the Command List Error
Table from the module. The format for the block is shown below:
Mailbox Request
Word
Offset in
Block
Data Field(s)
Description
0
Mailbox ID
This field contains the value of -9950 or 9950
identifying the block type to the module.
1
Number of
Commands to
report
This field contains the number of commands to
report in the response message. The value has
a range of 1 to 60.
2
Start Index of First
Command
This parameter sets the index in the command
list where to start. The first command in the list
has a value of 0. The last index in the list has a
value of MaxCommands - 1.
3 to 62
Spare
Not Used
63
Mailbox ID
This field contains the value of -9950 or 9950
identifying the block type to the module.