104C Version 3 ♦ ProLinx Gateway

Mailbox Feature (x201-DFNT-104C)

IEC 60870-5-104 Client (Firmware v3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 85 of 139

August 4, 2011

4.8

Set Gateway Time Mailbox (9971)

Mailbox identification code ±9971 is used to pass the date and time to the
module. The date and time provided will be used to set the 104 client drivers
clock.

Mailbox Request

Word Offset
in Block

Data Field(s)

Description

0

Mailbox ID

This field contains the block identification code of -9971 or 9971
for the block.

1

Year

This field contains the four-digit year to be used with the new
time value.

2

Month

This field contains the month value for the new time. Valid entry
for this field is in the range of 1 to 12.

3

Day

This field contains the day value for the new time. Valid entry for
this field is in the range of 1 to 31.

4

Hour

This field contains the hour value for the new time. Valid entry
for this field is in the range of 0 to 23.

5

Minute

This field contains the minute value for the new time. Valid entry
for this field is in the range of 0 to 59.

6

Seconds

This field contains the second value for the new time. Valid entry
for this field is in the range of 0 to 59.

7

Milliseconds

This field contains the millisecond value for the new time. Valid
entry for this field is in the range of 0 to 999.

8 to 62

Not Used

Not Used

63

Mailbox ID

This field contains the block identification code of -9971 or 9971
for the block.