Mailbox Feature (x201-DFNT-104C)

IEC 60870-5-104 Client (Firmware v3.xx)

Protocol Manual

ProSoft Technology, Inc.

Page 69 of 139

August 4, 2011

The same applies for the mailbox response. The module builds the mailbox
response and updates the mailbox ID according to the originating request:


Offset

Description

0

Mailbox ID

1

Start of mailbox response

62

End of mailbox response

63

Mailbox ID


The following mailboxes are supported by the module:

Block Range

Descriptions

±9901

User Constructed Command to add to command queue

±9902

Command Control Block (Add command to Command Queue)

±9903

Event Messages from Outstations

±9250

General Module Status

±9251

Client X Status Data

±9950

Command List Error data

±9970

Get 104 client driver's time

±9971

Set 104 client driver's time

±9997

Reset status data

9998

Cold boot Confirmation

9999

Cold Boot Request


The purpose for the mailbox supporting a positive and negative value is so the
remote device can trigger consecutive requests for the same mailbox by
switching the value between positive and negative. For example, to request 3
consecutive Get Module time the block ID could be switched as +9970, -9970,
+9970.