0 ~ 10vdc – LG C Series User Manual

Page 104

Advertising
background image

Chapter 11. Monitoring

Fault type

Operating status

when a fault

occurs

11.4 Analog Output

Group

LED

Display

Parameter Name

Set

value

Min/Max

range

Factory

default

Unit

I50

[Analog output item
select]

-

0/3 0

I/O group

I51

[Analog output level
adjustment]

- 10/200 100 %

ƒ Output item and the level from the AM terminal are selectable and adjustable.



I50: The selected item will be output to Analog output terminal (AM).

10V

0

Output
frequency.

Max Frequency (F21)

1

Output current

150% of Inverter rated current

2

Output voltage

282 Vac

I50 Analog

output

item select

3

Inverter DC link
voltage

400 Vdc



I51: If you want to use Analog output value as a gauge input, the value can be

adjustable corresponding to various gauge specifications.

AM

CM

0 ~ 10Vdc

104

Advertising