LG C Series User Manual

Page 50

Advertising
background image

Chapter 7. Function list

Function group 2

LED

display

Parameter

Name

Min/Max

Range

Description

Factory

defaults

Adjustable

during run

Page

H51

[P gain for
PID controller]

0/999.9
[%]

300.0 O

10-8

H52 [Integral

time

for PID
controller
(I gain)]

0.1/32.0
[sec]

1.0 O

10-8

H53 Differential

time for PID
controller
(D gain)

0.0 /30.0
[sec]

ƒ

This parameter sets the gains for the

PID controller.

0.0 O

10-8

H54

F gain for PID
controller

0/999.9
[%]

ƒ

This is the Feed forward gain for the PID

controller.

0.0 O

10-8

H55 [PID

output

frequency
limit]

0/400
[Hz]

ƒ

This parameter limits the amount of the

output frequency thru the PID control.

ƒ

The value is settable within the range of

F21 – [Max frequency] and H23 – [Start
frequency].

60.0 O

10-8

0

The Accel/Decel time is the time that
takes to reach the F21 – [Max
frequency] from 0 Hz.

H70 [Frequency

Reference for
Accel/Decel]

0/1

1

The Accel/Decel time is the time that
takes to reach a target frequency
from the run frequency.

0 X

9-10

0

Unit: 0.01 second.

1

Unit: 0.1 second.

H71 [Accel/Decel

time scale]

0/2

2

Unit: 1 second.

1 O

9-11

ƒ

This parameter selects the parameter to

be displayed on the keypad when the input
power is first applied.

0 Frequency

command

1 Accel

time

2 Decel

time

3 Drive

mode

4 Frequency

mode

5

Multi-Step frequency 1

6

Multi-Step frequency 2

7

Multi-Step frequency 3

8 Output

current

9 Motor

rpm

10

Inverter DC link voltage

11

User display select

12 Fault

display

H72 [Power

on

display]

0/13

13

Direction of motor rotation select

0 O

11-2

ƒ

One of the following can be monitored

via vOL - [User display select].

0 Output

voltage

[V]

1

Output power [kW]

H73 [Monitoring

item select]

0/2

2

Torque [kgf

⋅ m]

0 O

11-2

H74 [Gain

for

Motor rpm
display]

1/1000
[%]

ƒ

This parameter is used to change the

motor speed display to rotating speed
(r/min) or mechanical speed (m/mi).


100 O

11-1

H79 [Software

version]

0/10.0

ƒ

This parameter displays the inverter

software version.

X.X X

H81 [2

nd

motor

Accel time]

0/6000
[sec]

ƒ

This parameter is active when the

selected terminal is ON after I20-I24 is set

d

5.0 O

10-

16

100

74

31

120

H

H

f

RPM

Ч

Ч

=

50