10. Advanced functions

10.9 Sensorless vector control

Group

LED Display

Parameter Name

Set

value

Min/Max

Range

Factory

Defaults

Unit

H40

[Control mode select]

3

0/3 0

-

H30

[Motor type select]

- 0.2/2.2

- kW

H32

[Rated
slip frequency]

- 0/10

- Hz

H33

[Motor rated current]

- 1.0/12

- A

H34

[Motor No Load Current]

- 0.1/12

- A

H42

[Stator resistance (Rs)]

- 0/14.0

-

H44

[Leakage inductance
(L

σ)]

- 0/300.00

- mH

Function
group 2

F14

[Time for energizing a
motor]

- 0.0/60.0 1.0 Sec

ƒ If H40 – [Control mode select] is set to 3, Sensorless vector control will become active.

Caution :
Motor parameters should be measured for high performance. It is highly recommended H41 –
[Auto tuning] be done prior to proceeding operation via Sensorless vector control.



Ensure that the following parameters are entered correctly for high performance in

Sensorless vector control.



H30: Select motor type connected to inverter output.



H32: Enter rated slip frequency based on motor nameplate RPM and rated frequency.



H33: Enter motor nameplate rated current.



H34: After removing the motor load, select H40 – [Control mode select] to 0 {V/F

control} and run the motor at 60Hz. Enter the current displayed in Cur-[Output current]

as motor no load current. If it is difficult to remove the load from the motor shaft, enter

the value either 40 to 50% of the H33 – [Motor rated current] or the factory default.



H42, H44: Enter the value of the parameter measured during H41 – [Auto tuning] or the

factory default.



F14: This parameter accelerates the motor after pre-excitating the motor for the set time.

The amount of the excitating current is set in H34- [Motor no load current].