Parker Hannifin

116 Aries User Guide

DMTSWT

Motor temperature switch type

Type

Motor configuration

Product Rev

Syntax

<a_>DMTSWT<i>

Aries

2.10

Units

i = motor temp switch type

Range

0 (Normally closed switch)

1 (Positive temperature coefficient thermistor)
2 (Normally open switch)
3 (Negative temperature coefficient thermistor)

Default

DMTSWT0

Response

DMTSWT: <*>0

See Also

DTHERM

,

TMTEMP

DMTSWT sets the type of motor switch used. Values of 0 or 1 behave exactly
the same and are interchangeable. DMTSWT3 specifies a negative
temperature coefficient thermistor. In this case TMTEMP reports the higher of

the motor thermal model value or the calculated thermistor temperature,
once the thermistor temperature is above 60 degrees C. The drive faults with
a motor temperature fault at a thermistor temp of 105 degrees C or the motor
thermal model setpoint (whichever is lower) when DMTSWT is set to 3.

The default value for this command is DMTSWT0 and will work with both

positive temperature coefficient thermistors or normally closed switches.

DMTTCM

Motor Thermal Time Constant

Type

Motor

Product Rev

Syntax

<a_>DMTTCM<r>

Aries 1.0

Units

r = minutes

Range

Ш.Ш to 12Ш.Ш : ±Ш.1

Default

Ш.Ш

Response

DMTTCM: <*>3Ø.4

See Also

DMTR

,

DMTTCW

Auto-Setup

: When using a Parker motor and the Aries Support Tool, this

command is automatically set for the selected motor.
If you did not use the Aries Support Tool, are using non-Parker motors, or
sent an RFS command to the drive, the parameter is set to zero (0)—you

must manually set this parameter to a non-zero number.
For a list of auto-configured commands, see

DMTR

.

The DMTTCM command specifies the thermal time constant of the motor and

its mounting. The drive uses this value to help protect the motor from thermal
damage. It describes the length of time the motor takes to reach 63% of its
final temperature, given constant power. Note that the motor mounting
affects this measurement.

Continuous current ratings and published time constants for Parker motors
are specified when mounted to a 10" x 10" x ¼" aluminum plate in 25°C open
air. If your mounting surface provides heat-sinking or thermal mass
significantly different from this, a different value may be appropriate to your