Table 5 environmental specifications, ar-13xx, Cabinet cooling – Parker Hannifin 88-021610-01G User Manual

Page 23

Advertising
background image

Parker Hannifin

Chapter 2 Mechanical Installation 23

Environmental Specifications
(AR-01xx, AR-02xx, AR-04xx,
AR-08xx, AR-20xE, and AR-30xE)

Operating Temperature,
Maximum

Ambient Air

45°C (113°F)

Minimum 0°C

(32°F)

Storage Temperature

–40°C to 85°C (–40°F to 185°F)

Humidity

0 to 95%, non-condensing

Shock

15g, 11 ms half-sine

Vibration

10 to 2000 Hz at 2g

Pollution Degree

2 (per IEC 61010)

Installation Category

2 (per IEC 61010)

Table 4 Environmental Specifications, AR-01xx through AR-08xx, AR-20xE and AR-30xE

Environmental Specifications
(AR-13xx)

Operating Temperature,
Maximum

Ambient Air

40°C (104°F)

Minimum 0°C

(32°F)

Storage Temperature

–40°C to 85°C (–40°F to 185°F)

Humidity

0 to 95%, non-condensing

Shock

15g, 11 ms half-sine

Vibration

10 to 2000 Hz at 2g

Pollution Degree

2 (per IEC 61010)

Installation Category

2 (per IEC 61010)

Table 5 Environmental Specifications, AR-13xx

Cabinet Cooling

For cabinet cooling calculations, use Table 6 and Table 7 to determine the
power dissipation per drive.

AR-02xx

The power dissipation in Table 6 for the AR-02xx has been measured using
the Parker BE231D motor.

Advertising