P163, Outbd – Parker Hannifin 88-021610-01G User Manual

Page 137

Advertising
background image

Parker Hannifin

Chapter 6 Command Reference 137

OUTBD

Output Brake Delay

Type

Output

Product Rev

Syntax

<a_>OUTBD<i>

Aries

1.0

Units

milliseconds

Range

Ш-1ШШШШ

Default

Ø

Response

OUTBD: <*>25Ø

See Also

none

The OUTBD command specifies the amount of time that the brake relay will

remain asserted after the current is applied to the motor windings when the
drive is enabled. This allows torque to build up in the motor while the fault
output is still high. This is important in vertical applications where the motor
must be able to support the load before the brake is released.

P163

Hall direction P163

Type

Drive configuration

Product Rev

Syntax

<a_>P163<i>

Aries 1.0

Units

i = hall direction

Range

0 (Halls count 623154623… as encoder counts +ve)
1 (Halls count 326451326… as encoder counts +ve)

Default

0

Response

P163: <*>0

See Also

ENCOFF

,

SHALL

,

CMDDIR

,

ENCPOL

,

IANI

Note:

This command does not take effect until you cycle power to the drive,

or send the RESET command
The P163 command determines the order the Hall sensors count as the
encoder counts in a +ve direction. The default, P163=0, specifies that as the
encoder counts in a +ve direction that the Hall sensors count 6,2,3,1,5,4,6,…
P163=1 specifies that the hall sensors count in the opposite direction as the
encoder counts in the +ve direction.

This command has the same effect as swapping hall wires A and B to the
drive.