Parker Hannifin 88-021610-01G User Manual

Page 70

Advertising
background image

Parker Hannifin

70 Aries User Guide

Inputs—Enable, Reset

The drive Enable and Reset inputs are optically isolated inputs. Current is
limited internally for input voltage control of 5 to 24 volt logic. The Anode (+)
and Cathode (

−) are on separate connector pins to allow significant flexibility

in wiring to different styles of interface.

Description

Min

Max

Units

Turn-on time

1

ms

Turn-off time

1

ms

Guaranteed on voltage

4

VDC

Guaranteed off voltage

2

VDC

Maximum forward voltage

30

VDC

Maximum reverse voltage

-30

VDC

Forward current

3

12

mA

Note:

All parameters are at the connector pin.

Table 30 Inputs—Enable and Reset Electrical/Timing Characteristics

Outputs—Encoder

Description

Min

Typical

Max

Units

Output Frequency
(pre-quadrature)

5

MHz

Input Voltage High *

2.4

V

Input Voltage Low *

0.5

V

* Based on 120Ω differential load impedance.

Note:

All parameters are at the connector pin.

Note:

Aries encoder is a hardware pass-through; therefore, you cannot change output

resolution.

Table 31 Outputs—Encoder Outputs Electrical/Timing Characteristics

Outputs—Fault

Description

Min

Typical

Max

Units

Blocking Voltage

30

V

Continuous Load Current

10

mA

Output Saturation Voltage
(at 1.0 mA)

1.0

V

* Based on 120Ω differential load impedance.

Note:

All parameters are at the connector pin.

Table 32 Outputs— Fault outputs Electrical/Timing Characteristics

Advertising