Regeneration protection, Figure 25 external regeneration connection, Regeneration connection – Parker Hannifin 88-021610-01G User Manual

Page 54

Advertising
background image

Parker Hannifin

54 Aries User Guide

Regeneration Protection

The Aries drive models AR-20xE and AR-30xE have internal regeneration
power dump (dissipation) resistors. Models AR-01xx through AR-13xx do
not. However, all models can utilize an external regeneration resistor.

Regeneration Connection

To use a external regeneration (power dump) resistor, connect your external
resistor to the R+ and R- terminals as follows:

• For models AR-01x to AR-13xx, use the Mains connector.
• For models AR-20xE and AR-30xE, use the Control connector.

Figure 25 illustrates the external regeneration resistor connections.

Figure 25 External Regeneration Connection

Important!

For models AR-20xE and AR-30xE, you must remove the

factory-installed link between R

INT

and R

− when you connect the

external regeneration resistor. (Otherwise the internal regeneration
resistor will still be in the circuit, and its thermal protection circuit limits
the performance).

For information on selecting a suitable external regeneration (power dump)
resistor, see “Appendix B External Power-Dump Resistor Selection.”

Warning —

The drive’s connector strip terminals are at hazardous voltages

when power is applied to the drive, and up to several minutes after power is
removed. Lower voltages may still be present for several minutes after power
is removed.
During normal operation, these high voltage terminals must not be accessible
to the user.