Figure 41 clockwise/ counter-clockwise rotation, Config, Errors e10 – Parker Hannifin 88-021610-01G User Manual

Page 99

Advertising
background image

Parker Hannifin

Chapter 6 Command Reference 99

Rotary Motors

—Positive values represent

clockwise motion and negative values represent
counter-clockwise motion (assuming CMDDIR = Ø,

and that you connected the feedback device
according to instructions provided in “

Chapter 2

Mechanical Installation

” and “

Chapter 3 Electrical

Installation

”).

Figure 41 Clockwise/
Counter-clockwise rotation

CONFIG

Configuration Errors and Warnings

Type

Error Handling

Product Rev

Syntax

<a_>CONFIG

Aries 1.0

Units

N/A

Range

N/A

Default

N/A

Response

CONFIG <*>No

Errors

See Also

DMTIC

,

DMTIND

,

DMTIP

,

DMTW

,

ERROR


The CONFIG command gives a text-based status report of current
configuration errors and warnings (EØ through E24).

Error

Resolution

EØ—Motor Configuration
Warning

The motor rating is too high for the drive, and the
drive is using its own limits for safety reasons.

E1—Motor Configuration Error

One of the motor parameters is set to zero (0).
Look at the additional errors to find which
parameters are set at zero (0). Refer to your
motor specifications for the correct value.

E3—Max Inductance = Ø

This parameter is set to zero (0). To correct the
error, you must set a non-zero (0) value. Refer to
your motor specifications for the correct value.
(DMTIND)

E4—Rated Speed = Ø

This parameter is set to zero (0). To correct the
error, you must set a non-zero value. Refer to
your motor specifications for the correct value.
(DMTW)

E5—DPOLE = Ø

This parameter is set to zero (0). To correct the
error, you must set a non-zero value. Refer to
your motor specifications for the correct value.

(DPOLE)

E6—Resistance = Ø

This parameter is set to zero (0). To correct the
error, you must set a non-zero value. Refer to
your motor specifications for the correct value.
(DMTRES)

E7—Ke = Ø

This parameter is set to zero (0). To correct the
error, you must set a non-zero value. Refer to
your motor specifications for the correct value.
(DMKE)

E8—Continuous Current = Ø

This parameter is set to zero (0). To correct the
error, you must set a non-zero value. Refer to
your motor specifications for the correct value.
(DMTIC)