GE Industrial Solutions AF-600 FP High Power (460V_575V 150HP and above) User Manual

Page 10

Advertising
background image

Mains supply 3 x 380–480 V
Model number

AF-600 FP

450

500

550

600

AF-650 GP

350

450

500

550

Light duty current ratings (110%):
Output current

Nominal [A] (380–440 V)

600

658

745

800

MAX (60 sec) [A] (380–440 V)

660

724

820

880

Nominal [A] (441–480 V)

540

590

678

730

MAX (60 sec) [A] (441–480 V)

594

649

746

803

Output

Nominal [kVA] (400 V)

416

456

516

554

Nominal [kVA] (460 V)

430

470

540

582

Typical shaft output

[kW] (400 V)

315

355

400

450

[HP] (460 V)

450

500

550/600

600

Heavy duty torque (160%):
Output current

Nominal [A] (380–440 V)

480

600

658

695

MAX (60 sec) [A] (380–440 V)

720

900

987

1043

Nominal [A] (441–480 V)

443

540

590

678

MAX (60 sec) [A] (441–480 V)

665

810

885

1017

Output

Nominal [kVA] (400 V)

333

416

456

482

Nominal [kVA] (460 V)

353

430

470

540

Typical shaft output

[kW] (400 V)

250

315

355

400

[HP] (460 V)

350

450

500

550

Power loss Light duty [W]

6790

7701

8879

9670

Power loss Heavy duty [W]

5165

6960

7691

8636

Limits and Ranges
Overcurrent Warning

Drive A

RMS

Out

893

1169

1169

1301

Overcurrent Alarm (1.5 sec delay)

Drive A

RMS

Out

893

1169

1169

1301

Earth (Ground) Fault Alarm

Drive A

RMS

Out

265

322

352

405

Short Circuit Alarm

Drive A

RMS

Out

1138

1490

1490

1654

Heatsink Overtemperature

Degrees C

95

95

95

95

Heatsink Undertemperature Warning

Degrees C

0

0

0

0

Power Card Ambient Overtemperature

Degrees C

68

68

68

68

Power Card Ambient Undertemperature

Degrees C

-20

-20

-20

-20

Mains Phase Warning (5 sec delay)

DC Bus Ripple VAC

70

70

70

70

Mains Phase Alarm (25 sec delay)

DC Bus Ripple VAC

70

70

70

70

AF-650 GP and AF-600 FP High Power Service Manual

9

1