GE Industrial Solutions AF-600 FP High Power (460V_575V 150HP and above) User Manual

Page 83

Advertising
background image

Ohm test of fans

1.

Measure between terminals 11 and 13 of power card connector MK107. A reading of 20 ohms should be indicated.

2.

On IP21 and IP 54 units: Disconnect the spade connectors from the door fan and repeat the measurement. A reading of 21 ohms should be indicated.

3.

On IP21 and IP 54 units: Read the door fan terminals with the wires disconnected. A reading of 400 ohms should be indicated.

4.

Reconnect the wires to the door fan.

Incorrect reading
An incorrect reading of one or both of the fans indicates a defective fan. Replace the defective fan.

130BX80.10

1

2

3

Illustration 6.10: Fan Transformer and Fuse Location

380–480V: White label on fan transformer.

525–690V: Orange label on fan transformer.

1

Fan transformer

3

Fan fuse

2

CN2

AF-650 GP and AF-600 FP High Power Service Manual

82