4.

Remove the six retaining screws (T25) from the SCR/diode modules, terminals 2 and 3 in each module.

5.

Remove the 4 (10 mm) retaining nuts from the DC inductor input bus bars and the 4 retaining nuts (not shown) from the side mounted bus bars. (Side
mounted bus bars are only present on units with load sharing.) Remove the DC input bus assembly.

CONTINUED ON NEXT PAGE

130BX85.10

1

2

3

4

Illustration 7.1: 41/43 Soft Charge Resistor (2 of 3)

380–480V: Clear wire leads.

525–690V: Black wire leads.

1

Retaining screws (Step 4)

2

DC input bus assembly BB3

3

Retaining nuts (Step 5)

4

Soft charge resistor

AF-650 GP and AF-600 FP High Power Service Manual