6.2.10 Fan Continuity Tests: 5x-frame size

Make all continuity checks using an ohmmeter set to Rx1 scale. A digital or analog ohmmeter can be used. Some instability may result when measuring resistance
of a transformer with a multimeter. This can be reduced by turning off the auto-ranging function and setting the measurement manually.

To aid in making the measurements, unplug the MK107 from the power card.

Checking continuity of connections

For the following tests, read connector MK107 on the power card.

1.

Measure from L3 (T) to MK107 terminal 8. Reading of <1ohm should be indicated.

2.

Measure from L2 (S) to MK107 terminal 1. Reading of <1 ohm should be indicated.

Incorrect reading
An incorrect reading would indicate a faulty cable connection. Replace the cable assembly.

Fan fuse test

1.

Test the fan fuses on the power card mounting plate by checking the continuity across the fuse.

An open fuse could indicate additional faults. Replace the fuse and continue the fan checks.

Ohm test of transformer

For the following tests, read the plug end of the wire connected to MK107 on the power card.

1.

Measure between MK107 terminals 1 and 8. Should read approximately value A in Table 6-1.

2.

Measure between MK107 terminals 8 and 12. Should read approximately value B in Table 6-1.

3.

Measure between MK107 terminals 1 and 12. Should read approximately value C in Table 6-1.

AC Voltage

Drive

Resistance (in Ohms)

Heatsink Fan

Fan Inductor

AF-600 FP

AF-650 GP

A

B

C

D

380-480

450

350

15

12

4

21

no

380-480

500

450

4

3

1

4

yes

380-480

550

500

4

3

1

4

yes

380-480

600

550

4

3

1

4

yes

525-690

450

500

20

8

12

21

no

525-690

500

500

20

8

12

21

no

525-690

600

600

7.4

3.6

3.2

4

yes

525-690

650

650

7.4

3.6

3.2

4

yes

Table 6.1: Fan transformer resistance

Incorrect reading
An incorrect reading would indicate a defective fan transformer. Replace the fan transformer.

When finished, reconnect the MK107.

AF-650 GP and AF-600 FP High Power Service Manual