GE Industrial Solutions AF-600 FP High Power (460V_575V 150HP and above) User Manual
Page 12
Mains supply 3 x 525–690 V
1.
Model number
AF-600 FP
450
500
600
650
AF-650 GP 450
500
600
650
Light duty current ratings (110%):
Output current
Nominal [A] (525–550 V)
470
523
596
630
MAX (60 sec) [A] (525–550 V)
517
575
656
693
Nominal [A] (551–690 V)
450
500
570
630
MAX (60 sec) [A] (551–690 V)
495
550
627
693
Output
Nominal [kVA] (550 V)
448
498
568
600
Nominal [kVA] (575 V)
448
498
568
627
Nominal [kVA] (690 V)
538
598
681
753
Typical shaft output
[kW] (550 V)
355
400
450
500
[HP] (575 V)
450
500
600
650
[kW] (690 V)
450
500
560
630
Heavy duty torque (160%):
Output current
Nominal [A] (525–550 V)
395
429
523
596
MAX (60 sec) [A] (525–550 V)
593
644
785
894
Nominal [A] (551–690 V)
380
410
500
570
MAX (60 sec) [A] (551–690 V)
570
615
750
855
Output
Nominal [kVA] (550 V)
376
409
498
568
Nominal [kVA] (575 V)
376
408
498
568
Nominal [kVA] (690 V)
454
490
598
681
Typical shaft output
[kW] (550 V)
315
315
400
450
[HP] (575 V)
400
400
500
600
[kW] (690 V)
355
400
500
560
Power loss Light duty [W]
6449
7249
8727
9673
Power loss Heavy duty [W]
5383
5818
7671
8715
Limits and Ranges
Overcurrent Warning
Drive A
RMS
Out
824
824
989
1168
Overcurrent Alarm (1.5 sec delay)
Drive A
RMS
Out
824
824
989
1168
Earth (Ground) Fault Alarm
Drive A
RMS
Out
190
205
250
285
Short Circuit Alarm
Drive A
RMS
Out
1046
1046
1255
1490
Heatsink Overtemperature
Degrees C
85
85
85
85
Heatsink Undertemperature Warning
Degrees C
0
0
0
0
Power Card Ambient Overtemperature
Degrees C
68
68
68
68
Power Card Ambient Undertemperature
Degrees C
-20
-20
-20
-20
Mains Phase Warning (5 sec delay)
DC Bus Ripple VAC
70
70
70
70
Mains Phase Alarm (25 sec delay)
DC Bus Ripple VAC
70
70
70
70
1.
AF-600 FP only available up to 600 V
AF-650 GP and AF-600 FP High Power Service Manual
11
1