7.
Note which gate leads attach to which module for reassembly. Remove the SCR/diode gate lead connectors from the modules (not shown).
8.
If the unit is equipped with a brake option, remove the two bus bars attaching the brake IGBT module to the IGBT bus assy. Remove the SCR/diode
mounting screws.
130BX92.10
1
2
Illustration 7.1: 41/43 SCR/Diode Module (3 of 3)
1
SCR/diode module
2
Mounting screws (Step 8)
REASSEMBLY
1.
To replace SCR/diode modules, follow the instructions included with the replacement module.
2.
Reinstall the module and mounting screws. Tighten the remaining T25 and 8 mm screws to 2.3 Nm (20 in-lbs) and T30 and 10 mm to 4 Nm (35 in-lbs).
3.
Reassemble the remaining parts in reverse order of their removal.