GE Industrial Solutions AF-600 FP High Power (460V_575V 150HP and above) User Manual

Page 63

Advertising
background image

motor. At this point the motor becomes a generator and starts returning energy to the frequency converter. This is called regenerative energy. Regeneration
occurs when the speed of the load is greater than the commanded speed. This return voltage is rectified by the diodes in the IGBT modules and raises the DC bus.
If the amount of returned voltage is too high, the frequency converter will trip.

There are a few ways to overcome this situation. One method is to reduce the deceleration rate so it takes longer for the frequency converter to decelerate. A
general rule of thumb is that the frequency converter can only decelerate the load slightly faster than it would take for the load to naturally coast to a stop. A
second method is to allow the overvoltage control circuit to take care of the deceleration ramp. When enabled the overvoltage control circuit regulates deceleration
at a rate that maintains the DC bus voltage at an acceptable level. One caution with overvoltage control is that it will not make corrections to unrealistic ramp
rates. For example, if the deceleration ramp needs to be 100 seconds due to the inertia, and the ramp rate is set at 3 seconds, overvoltage control will initially
engage and then disengage and allow the frequency converter to trip. This is purposely done so the units operation is not misinterpreted. A third method in
controlling regenerated energy is with a dynamic brake. The frequency converter monitors the level of the DC bus. Should the level become too high, the frequency
converter switches the resistor across the DC bus and dissipates the unwanted energy into the external resistor bank mounted outside of the frequency converter.
This will actually increase the rate of deceleration.

Less often is the case that the overvoltage condition is caused by the load while it is running at speed. In this case the dynamic brake option can be used or the
overvoltage control circuit. It works with the load in this way. As stated earlier, regeneration occurs when the speed of the load is greater than the commanded
speed. Should the load become regenerative while the frequency converter is running at a steady state speed, the overvoltage circuit will increase the frequency
to match the speed of the load. The same restriction on the amount of influence applies. The frequency converter will add about 10% to the base speed before
a trip occurs. Otherwise, the speed could continue to rise to potentially unsafe levels.

5.1.2 Mains Phase Loss Trips

The frequency converter actually monitors phase loss by monitoring the amount of ripple voltage on the DC bus. Ripple voltage on the DC bus is a product of a
phase loss. The main concern is that ripple voltage causes overheating in the DC bus capacitors and the DC coil. Left unchecked, the lifetime of the capacitors
and DC coil would be drastically reduced.

When the input voltage becomes unbalanced or a phase disappears completely, the ripple voltage increases causing the frequency converter to trip and issue
an Alarm 4. In addition to missing phase voltage, increased bus ripple can be caused by a line disturbance or imbalance. Line disturbances may be caused by
line notching, defective transformers or other loads that may be effecting the form factor of the AC waveform. Mains imbalances which exceed 3% cause sufficient
DC bus ripple to initiate a trip.

Output disturbances can have the same effect of increased ripple voltage on the DC bus. A missing or lower than normal output voltage on one phase can cause
increased ripple on the DC bus. Should a mains imbalance trip occur, it is necessary to check both the input and output voltage of the frequency converter.

Severe imbalance of supply voltage or phase loss can easily be detected with a voltmeter. Line disturbances most likely need to be viewed on an oscilloscope.
Conduct tests for input imbalance of supply voltage, input waveform, and output imbalance of supply voltage as described in the chapter Troubleshooting.

5.1.3 Control Logic Problems

Problems with control logic can often be difficult to diagnose, since there is usually no associated fault indication. The typical complaint is simply that the frequency
converter does not respond to a given command. There are two basic commands that must be given to any frequency converter in order to obtain an output.
First, the frequency converter must be told to run (start command). Second, the frequency converter must be told how fast to run (reference or speed command).

The frequency converters are designed to accept a variety of signals. First determine what types of signals the frequency converter is receiving. There are six
digital inputs (terminals 18, 19, 27, 29, 32, 33), two analog inputs (53 and 54), and the network (68, 69). The presence of a correct reading will indicate that the
desired signal has been detected by the microprocessor of the frequency converter. See the chapter Frequency Converter Inputs and Outputs.

Using the status information displayed by the frequency converter is the best method of locating problems of this nature. By selecting within parameter group
K-2# Keypad Display, line 2 or 3 of the display can be set to indicate the signals coming in. The presence of a correct reading indicates that the desired signal is
detected by the microprocessor of the frequency converter. This data also may be read in parameter group DR-6#.

If there is not a correct indication, the next step is to determine whether the signal is present at the input terminals of the frequency converter. This can be
performed with a voltmeter or oscilloscope in accordance with the 6.3.16, Input Terminal Signal Test.

AF-650 GP and AF-600 FP High Power Service Manual

62

5

Advertising