Illustration 8.1: Control Card Access

380–480V: Yellow tape on the main SMPS transformer in the upper right cor-
ner.

525–690V: White tape on the main SMPS transformer in the upper right cor-
ner.

1

Keypad(Step 2)

8

Power card PCA3

2

Keypad cradle (Step 3)

9

MK102 ring lug connection

3

C-option (if installed)

10

DC bus fuse

4

Mounting screws (Step 5)

11

Control card mounting plate

5

Control assembly support bracket

12

Control card terminal block

6

Attaching hardware

13

Control card (under Keypad)

7

Power card mounting plate

8.2.2 Control Assembly Support Bracket

1.

Remove the control card mounting plate in accordance with procedure.

2.

Remove the 6 mounting nuts (10 mm), see Illustration 8-1.

3.

Remove the control assembly support bracket.

Reinstall in reverse order of this procedure. Tighten the mounting screws to 4 Nm (35 in-lbs).