8. Remove the 4 (10 mm) retaining nuts at the top of the IGBT bus bar assy.

9. Remove the 6 retaining screws on the upper portion of the IGBT modules. These screws also attach the snubber capacitors to the IGBT modules.
Remove the 3 snubber capacitors.

10. Remove the IGBT bus bar assy.

11. At the bottom end of a IGBT module, remove the 6 retaining screws (2 each for U, V, and W intermediate IGBT output bus bars).

12. Remove the retaining nut (8 mm) from the 3 intermediate IGBT output bus bars. Remove the intermediate IGBT output bus bars.

13. Remove the IGBT module.

14. Clean the heatsink surface with a mild solvent or alcohol solution.

REASSEMBLY

1.

Replace the IGBT module in accordance with the instructions enclosed with the replacement module.

2.

Tighten the remaining T25 and 8 mm screws to 2.3 Nm (20 in-lbs) and T30 and 10 mm to 4 Nm (35 in-lbs).

3.

Reassemble the frequency converter in reverse order of disassembly and tighten the attachment hardware in accordance with the torque tables.

130BX159.10

1

2

3

4

5

6

7

Illustration 7.1: 41/43 IGBT Module (2 of 2)

1

IGBT module

5

Retaining screw (Step 9)

2

Snubber capacitor (Step 9)

6

Retaining nut (Step 11)

3

IGBT bus bar assembly (Step 8)

7

Intermediate IGBT output bus bar (Step 11)

4

Retaining nut (Step 8)

AF-650 GP and AF-600 FP High Power Service Manual

128

7

Advertising