15 fan tests – GE Industrial Solutions AF-600 FP High Power (460V_575V 150HP and above) User Manual

Page 98

Advertising
background image

If an incorrect reading was obtained from the above tests, further tests of the current feedback signals are required using the signal test board.

Testing current feedback with the signal test board.

8. Remove power to frequency converter. Make sure the DC bus is fully discharged.

9. Install the signal test board into power card connector MK104.

10. Using a DVM, measure the resistance between terminals 1 and 4, 2 and 4, and 3 and 4 of the signal test board. Resistance should be the same for
all three readings. Table 6-2 shows approximate resistance readings based on frequency converter power and voltage rating. Note that values listed
are values at the current scaling card. When measuring with a signal test board, the actual reading may be higher due to meter lead resistance. Absence
of resistance indicates a missing scaling card.

11. Reapply power to the frequency converter.

12. Using a DVM, connect the negative (-) meter lead to terminal 4 (common) of the signal test board.

13. Run the frequency converter with a zero speed reference.

14. Measure the AC voltage at terminals 1, 2, and 3 of the signal test board in sequence. These terminals correspond with current sensor outputs U, V,
and W, respectively. Expect a reading near zero volts but no greater than 15 mv.

If the control card parameters are set up to provide holding torque while at zero speed, the current displayed will be greater than expected. To perform this test,
disable such parameters.

The current sensor feedback signal at this point in the circuit will read approximately 400 mv at a 100% frequency converter load so any reading above 15 mv
while the frequency converter is at zero speed has a negative effect on the way the frequency converter interprets the feedback signal.

A reading of greater than 15 mv suggests that the corresponding current sensor be replaced. See the disassembly instructions in Section 7 or 8.

Voltage (AC)

AF-600 FP

AF-650 GP

Resistance (Ohms)

380-480

150

125

4.5

380-480

200

150

3.8

380-480

250

200

3.1

380-480

300

250

2.6

380-480

350

300

5.1

380-480

450

350

4.2

380-480

500

450

2.6

380-480

550

500

2.6

380-480

600

550

2.3

525-690

125

5.9

525-690

150

150

5.9

525-690

200

200

4.5

525-690

250

250

3.1

525-690

300

300

3.1

525-690

350

350

2.6

525-690

400

400

5.1

525-690

450

450

4.5

525-690

500

500

4.5

525-690

600

600

3.8

525-690

650

650

2.6

Table 6.3: Scaling Card Resistance Values
AF-600 FP only up to 600 V

6.3.15 Fan Tests

The fan control circuit is made up of the fan transformer and the control circuitry located on the power card along with control signals for ON, OFF, and speed
control from the control card. Since the fans do not necessarily run at all times, see the description for cooling fan operation under sequence of operation in
Section 3.3.5.

AF-650 GP and AF-600 FP High Power Service Manual

97

6

Advertising